BUILDING AND MEP REVIEW
3D model review
Federated BIM review: native MEP model with separate architecture / structure models, discipline switches, transparent walls and ceilings, section box, level isolation, system and category filters, room and equipment search, indicative clashes, element properties and links to drawings, schedules and calculations.
Equipment completeness — scheduled equipment vs the native Revit model (103 scheduled tags; HP-01: MISSING)
The heat pump HP-01 is not in this accepted native model (MISSING). It exists only as a PROPOSED catalogue-candidate envelope in the proposed native plant model, which is not adopted. View HP-01 in the proposed model →
NATIVE-EXPORTED MEP GEOMETRY — tessellated by Revit from model b2d7fae04a09… (wf1-NATIVE-REVIT-APS-MEP-20261019-1ce22c7e; export geom-inputs-20261021; verdict PARTIAL)
SYNTHETIC ARCHITECTURE — not architect-issued, not as-built; generated by Hexanta from the synthetic case geometry (wf1-SYNTHETIC-ARCH-MODEL-20261021-r2). A separate model; the native MEP model is unchanged.
NOT HELD — not drawn: NOT HELD: DoorsNOT HELD: WindowsNOT HELD: Wall / slab / roof thicknesses and constructionsNOT HELD: Structure (grids, columns, beams)NOT HELD: Plantroom ceilingNOT HELD: Stairs, lift shaft, cores
Display assumptions (not held data): slab thickness 250 mm (display only)
Not held — not drawn (6)
- Doors: no door positions or sizes in the case geometry
- Windows: only glazing areas per room (case fabric) and the WWR are held; no window positions or sizes — not drawn
- Wall / slab / roof thicknesses and constructions: U-values only; surfaces drawn at the case lines
- Structure (grids, columns, beams): no structural model or grid held
- Plantroom ceiling: design basis: 'wx-07 drops inside the plantroom at x 42.9 (crossing oa-m1 and gx-m1 there, where there is no ceiling) and enters r07 through the east wall at y 7.5' — plantroom ceiling not drawn
- Stairs, lift shaft, cores: not in the case geometry
- Unresolved: Plantroom r09 clear height — case.json states clear height 3.2 m; the soffit working assumption is 3.6 m. The model draws the soffit at 3.6 m (the later design-basis assumption); the difference is unresolved pending architect / structural confirmation
Rooms (12) — names, areas and level from the case geometry (SYNTHETIC)
| Room | Name | Use | Area (m²) | Level |
|---|---|---|---|---|
| r01a | Open-plan office zone 1 | office | 135 | Ground Floor |
| r01b | Open-plan office zone 2 | office | 135 | Ground Floor |
| r01c | Open-plan office zone 3 | office | 135 | Ground Floor |
| r01d | Open-plan office zone 4 | office | 135 | Ground Floor |
| r02 | Meeting room 1 | meeting | 36 | Ground Floor |
| r03 | Meeting room 2 | meeting | 36 | Ground Floor |
| r04 | Reception | circulation | 36 | Ground Floor |
| r05 | WC female | wc | 30 | Ground Floor |
| r06 | WC male | wc | 30 | Ground Floor |
| r07 | Accessible WC | wc | 18 | Ground Floor |
| r08 | East lift lobby | circulation | 30 | Ground Floor |
| r09 | Mechanical plantroom (plantroom) | plant | 108 | Ground Floor |
Coloured services: NATIVE Revit MEP geometryGrey and brown building: SYNTHETIC architecture, not architect-issued