BUILDING AND MEP REVIEW

Proposed model comparison

The accepted Run 4 native model beside a PROPOSED native model that adds provisional plant planning envelopes and PROVISIONAL plant connections, both federated with the same SYNTHETIC architectural model (roof, walls, partitions, ceilings, floor). The proposed model is for review only and does not replace the accepted baseline.

Heat pump HP-01 — PROPOSED planning envelope, not installed or validated

HP-01 appears only in the PROPOSED native model (wf1-NATIVE-REVIT-APS-MEP-20261022-d427192e), as a catalogue-candidate envelope "HXA Catalogue Candidate Envelope + Provisional Interfaces" of 1.10 × 3.34 × 1.88 m on the Ground Floor. It is not in the accepted Run 4 native model, is not a manufacturer selection, has not been adopted and has no engineering approval. Location: Option A external ground-level compound east of the plantroom — SYNTHETIC / SUBJECT TO ARCHITECTURAL, ACOUSTIC AND ENGINEERING REVIEW. No plant-compound or screen geometry exists; its electrical supply, BMS and defrost interfaces are recorded as BLOCKED.

Use Plant area · HP-01 in the PROPOSED viewer below to frame and select it with its external connection point.

PROPOSED — NOT ADOPTED

SYNTHETIC / SUBJECT TO ARCHITECTURAL, ACOUSTIC AND ENGINEERING REVIEW. D-S4-PLANT-R2-A (Option A provisional synthetic planning basis) + r3 PROVISIONAL plant connection design (wf1-PLANT-CONNECTION-DESIGN-20261022-r5); not architect-approved, manufacturer-verified, engineer-approved or construction-ready. The accepted model (wf1-NATIVE-REVIT-APS-MEP-20261019-1ce22c7e) is unchanged and remains the Run 4 baseline; this proposed model (wf1-NATIVE-REVIT-APS-MEP-20261022-d427192e, geometry wf1-NATIVE-REVIT-APS-GEOM-20261022-3ac55842, PARTIAL) is for review only.

Provisional planning envelopes only: no manufacturer selection, no connectors and no plant pipework connections are modelled.

1312 of 1312 accepted elements unchanged · 82 added · 0 removed or changed (match: category, family, type, size, mark and bounding box (1 mm)).

Added in the proposed model (82 elements)
Added in the proposed model
MarkCategoryFamily / typeSize (bounding box)Data status
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1000 × 89 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1000 × 89 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1000 × 60 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1000 × 60 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 89 × 1524 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 1398 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)348 × 89 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 89 × 224 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 89 × 374 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)548 × 89 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 1798 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 89 × 1674 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 60 × 1992 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 4334 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)384 × 60 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 60 × 692 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 60 × 842 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)584 × 60 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 4734 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 60 × 2142 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 89 × 224 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 1148 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1948 × 89 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 89 × 1024 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 89 × 1324 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1648 × 89 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 1024 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 324 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)3048 × 89 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 848 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1148 × 89 × 89 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)89 × 89 × 724 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 60 × 242 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 184 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1984 × 60 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 60 × 1042 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 60 × 1342 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)1684 × 60 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 242 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 1342 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)4384 × 60 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 284 × 60 mm—
—PipesPipe Types / HXA Steel Pipe (WF1 DN range)60 × 60 × 742 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard89 × 121 × 121 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 121 × 89 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 89 × 121 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 89 × 121 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 121 × 89 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard89 × 121 × 121 mm—
—Pipe FittingsElbow - Threaded - MI / Standard75 × 96 × 96 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 96 × 75 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 75 × 96 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 75 × 96 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 96 × 75 mm—
—Pipe FittingsElbow - Threaded - MI / Standard75 × 96 × 96 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard89 × 121 × 121 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 121 × 89 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 89 × 121 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 89 × 121 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 121 × 89 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 121 × 89 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 121 × 89 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 121 × 89 mm—
—Pipe FittingsElbow - Butt Welded - CS / Standard121 × 89 × 121 mm—
—Pipe FittingsElbow - Threaded - MI / Standard75 × 96 × 96 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 96 × 75 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 75 × 96 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 75 × 96 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 96 × 75 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 96 × 75 mm—
—Pipe FittingsElbow - Threaded - MI / Standard96 × 96 × 75 mm—
—Pipe FittingsElbow - Threaded - MI / Standard75 × 96 × 96 mm—
MCP-01Mechanical EquipmentHXA Plan Control Panel / HXA Planning Envelope600 × 3000 × 2000 mmPROVISIONAL
BV-CHWMechanical EquipmentHXA Plan Buffer Vessel Chw IF / HXA Planning Envelope + Provisional Interfaces800 × 800 × 1800 mmPROVISIONAL
BV-LTHWMechanical EquipmentHXA Plan Buffer Vessel Lthw IF / HXA Planning Envelope + Provisional Interfaces800 × 800 × 1800 mmPROVISIONAL
DP-01-02Mechanical EquipmentHXA Plan Dosing Pot / HXA Planning Envelope600 × 800 × 1200 mmPROVISIONAL
HDR-01Mechanical EquipmentHXA Plan Header IF / HXA Planning Envelope + Provisional Interfaces400 × 2000 × 1500 mmPROVISIONAL
PU-01-02Mechanical EquipmentHXA Plan Pressurisation Unit / HXA Planning Envelope1400 × 1200 × 1500 mmPROVISIONAL
XP-CONNMechanical EquipmentHXA Plan External Connection IF / HXA Planning Envelope + Provisional Interfaces400 × 800 × 500 mmPROVISIONAL
CHWP-01A-BMechanical EquipmentHXA Plan Pump Set Chw IF / HXA Planning Envelope + Provisional Interfaces1400 × 1000 × 1000 mmPROVISIONAL
LTHWP-01A-BMechanical EquipmentHXA Plan Pump Set Lthw IF / HXA Planning Envelope + Provisional Interfaces1400 × 1000 × 1000 mmPROVISIONAL
HP-01Mechanical EquipmentHXA Plan Heat Pump Candidate IF / HXA Catalogue Candidate Envelope + Provisional Interfaces1100 × 3342 × 1875 mmPROVISIONAL
Elements by category
CategoryAcceptedProposed
Air Terminals3333
Duct Fittings190190
Ducts204204
Mechanical Equipment1727
Pipe Fittings398427
Pipes458501
Spaces1212

Accepted — Run 4 baseline

NATIVE-EXPORTED MEP GEOMETRY — tessellated by Revit from model b2d7fae04a09… (wf1-NATIVE-REVIT-APS-MEP-20261019-1ce22c7e; export geom-inputs-20261021; verdict PARTIAL)

SYNTHETIC ARCHITECTURE — not architect-issued, not as-built; generated by Hexanta from the synthetic case geometry (wf1-SYNTHETIC-ARCH-MODEL-20261021-r2). A separate model; the native MEP model is unchanged.

NOT HELD — not drawn: NOT HELD: DoorsNOT HELD: WindowsNOT HELD: Wall / slab / roof thicknesses and constructionsNOT HELD: Structure (grids, columns, beams)NOT HELD: Plantroom ceilingNOT HELD: Stairs, lift shaft, cores

Display assumptions (not held data): slab thickness 250 mm (display only)

Not held — not drawn (6)
  • Doors: no door positions or sizes in the case geometry
  • Windows: only glazing areas per room (case fabric) and the WWR are held; no window positions or sizes — not drawn
  • Wall / slab / roof thicknesses and constructions: U-values only; surfaces drawn at the case lines
  • Structure (grids, columns, beams): no structural model or grid held
  • Plantroom ceiling: design basis: 'wx-07 drops inside the plantroom at x 42.9 (crossing oa-m1 and gx-m1 there, where there is no ceiling) and enters r07 through the east wall at y 7.5' — plantroom ceiling not drawn
  • Stairs, lift shaft, cores: not in the case geometry
  • Unresolved: Plantroom r09 clear height — case.json states clear height 3.2 m; the soffit working assumption is 3.6 m. The model draws the soffit at 3.6 m (the later design-basis assumption); the difference is unresolved pending architect / structural confirmation
Loading geometry…
SYNTHETIC — not architect-issued (case geometry; partitions darker, envelope lighter)
Rooms (12) — names, areas and level from the case geometry (SYNTHETIC)
RoomNameUseArea (m²)Level
r01aOpen-plan office zone 1office135Ground Floor
r01bOpen-plan office zone 2office135Ground Floor
r01cOpen-plan office zone 3office135Ground Floor
r01dOpen-plan office zone 4office135Ground Floor
r02Meeting room 1meeting36Ground Floor
r03Meeting room 2meeting36Ground Floor
r04Receptioncirculation36Ground Floor
r05WC femalewc30Ground Floor
r06WC malewc30Ground Floor
r07Accessible WCwc18Ground Floor
r08East lift lobbycirculation30Ground Floor
r09Mechanical plantroom (plantroom)plant108Ground Floor

Coloured services: NATIVE Revit MEP geometryGrey and brown building: SYNTHETIC architecture, not architect-issued

PROPOSED — provisional plant and connections (not adopted)

NATIVE-EXPORTED MEP GEOMETRY — tessellated by Revit from model b8074ad75bb2… (wf1-NATIVE-REVIT-APS-MEP-20261022-d427192e; export geom-proposed-d427192e; verdict PARTIAL)

SYNTHETIC ARCHITECTURE — not architect-issued, not as-built; generated by Hexanta from the synthetic case geometry (wf1-SYNTHETIC-ARCH-MODEL-20261021-r2). A separate model; the native MEP model is unchanged.

NOT HELD — not drawn: NOT HELD: DoorsNOT HELD: WindowsNOT HELD: Wall / slab / roof thicknesses and constructionsNOT HELD: Structure (grids, columns, beams)NOT HELD: Plantroom ceilingNOT HELD: Stairs, lift shaft, cores

Display assumptions (not held data): slab thickness 250 mm (display only)

Not held — not drawn (6)
  • Doors: no door positions or sizes in the case geometry
  • Windows: only glazing areas per room (case fabric) and the WWR are held; no window positions or sizes — not drawn
  • Wall / slab / roof thicknesses and constructions: U-values only; surfaces drawn at the case lines
  • Structure (grids, columns, beams): no structural model or grid held
  • Plantroom ceiling: design basis: 'wx-07 drops inside the plantroom at x 42.9 (crossing oa-m1 and gx-m1 there, where there is no ceiling) and enters r07 through the east wall at y 7.5' — plantroom ceiling not drawn
  • Stairs, lift shaft, cores: not in the case geometry
  • Unresolved: Plantroom r09 clear height — case.json states clear height 3.2 m; the soffit working assumption is 3.6 m. The model draws the soffit at 3.6 m (the later design-basis assumption); the difference is unresolved pending architect / structural confirmation
Loading geometry…
SYNTHETIC — not architect-issued (case geometry; partitions darker, envelope lighter)
Rooms (12) — names, areas and level from the case geometry (SYNTHETIC)
RoomNameUseArea (m²)Level
r01aOpen-plan office zone 1office135Ground Floor
r01bOpen-plan office zone 2office135Ground Floor
r01cOpen-plan office zone 3office135Ground Floor
r01dOpen-plan office zone 4office135Ground Floor
r02Meeting room 1meeting36Ground Floor
r03Meeting room 2meeting36Ground Floor
r04Receptioncirculation36Ground Floor
r05WC femalewc30Ground Floor
r06WC malewc30Ground Floor
r07Accessible WCwc18Ground Floor
r08East lift lobbycirculation30Ground Floor
r09Mechanical plantroom (plantroom)plant108Ground Floor

Coloured services: NATIVE Revit MEP geometryGrey and brown building: SYNTHETIC architecture, not architect-issued

Plant detail — connection register

PROPOSED r3 — PROVISIONAL connection design; not engineer-approved, not for construction

SYNTHETIC / SUBJECT TO ARCHITECTURAL, ACOUSTIC AND ENGINEERING REVIEW. D-S4-PLANT-R2-A (Option A, provisional synthetic planning basis); design model plantroom.primary_routes (CANDIDATE, MF-1 + MF-3) Register wf1-PLANT-CONNECTION-DESIGN-20261022-r6 (SHA-256 e38ae6bf1c03…); native status against wf1-NATIVE-REVIT-APS-GEOM-20261022-3ac55842 — connected natively = the PROPOSED native MEP run's own read-back reports every equipment end of the item's run as '<element>.<connector> connected to <run>' (outcome.json Checks); some ends only: PARTIAL; none: NOT YET NATIVE.

4 VERIFIED · 27 PROVISIONAL · 9 BLOCKED

HP-01

Status
PROVISIONAL PROVISIONAL planning envelope (PROPOSED model; not adopted)
Location
Option A external ground-level compound east of the plantroom — SYNTHETIC / SUBJECT TO ARCHITECTURAL, ACOUSTIC AND ENGINEERING REVIEW
Envelope (bbox, m)
[49.000, 0.600, 0.000, 50.100, 3.942, 1.875] (1100 × 3342 × 1875 mm)
Compound
zone: NOT HELD · screen: NOT HELD · gate: maintenance gate on the east side; external approach to the site ASSUMED · service_corridor: NOT HELD
Manufacturer
CONFIRMATION REQUIRED (catalogue candidate; not selected)

Intended CHW / LTHW connections

ConnectionSizeCategoryNative status
HP-01 ↔ XP-CONN external primary — CHW FLOW
HP-01.chw_flow_out → XP-CONN.chw_flow_ext
DN80PROVISIONALConnected natively
HP-01 ↔ XP-CONN external primary — CHW RETURN
XP-CONN.chw_return_ext → HP-01.chw_return_in
DN80PROVISIONALConnected natively
HP-01 ↔ XP-CONN external primary — LTHW FLOW
HP-01.lthw_flow_out → XP-CONN.lthw_flow_ext
DN50PROVISIONALConnected natively
HP-01 ↔ XP-CONN external primary — LTHW RETURN
XP-CONN.lthw_return_ext → HP-01.lthw_return_in
DN50PROVISIONALConnected natively

Other interfaces

  • VERIFIED HP-01 CHW connection size 2 1/2" grooved — Published data sheet (catalogue record aermec-nrp-0600-a-4pipe): 2 1/2" grooved (source S1); position NOT HELD
  • VERIFIED HP-01 full-load current 100 A (data sheet) — Published data sheet value; selection CONFIRMATION REQUIRED
  • BLOCKED HP-01 electrical supply, isolator and route — No electrical design / LV distribution model; supply route NOT HELD
  • BLOCKED HP-01 controls / BMS interface — Interface (protocol, points) NOT HELD; controls schematic INDICATIVE
  • BLOCKED HP-01 defrost / condensate drainage — Drain point, falls and frost protection NOT HELD (public health engineer)

Engineering duties

Selected heating duty
56.8 kW
Selected cooling duty
106.1 kW
Margin
20 % (plant_selection.margin_option = 20 %; applied once, to the base duty)
Heat source (proposed)
external four-pipe (polyvalent) air-source heat pump providing CHW and LTHW simultaneously; heat-recovery mode when both are needed
Published catalogue capacity (candidate, not selected)
cooling 123.7 kW at chw_out_in_c 7/12, ambient_c 35 (published)
Published catalogue capacity (candidate, not selected)
heating 137.3 kW at ambient_c 7, lthw_in_out_c 40/45 (published)

Related drawings (P08 proposed plant revision)

Schedules

Outstanding / blocked

  • PROVISIONAL HP-01 ↔ XP-CONN external primary — CHW FLOW
  • PROVISIONAL HP-01 ↔ XP-CONN external primary — CHW RETURN
  • PROVISIONAL HP-01 ↔ XP-CONN external primary — LTHW FLOW
  • PROVISIONAL HP-01 ↔ XP-CONN external primary — LTHW RETURN
  • BLOCKED HP-01 electrical supply, isolator and route
  • BLOCKED HP-01 controls / BMS interface
  • BLOCKED HP-01 defrost / condensate drainage

Connections

VERIFIED 4 — supported by the engineering model, calculations and manufacturer data
ItemSystemSizeNative statusBasis / pending
NET-DIST
Existing CHW / LTHW distribution (112 runs, Run 4)
CHW+LTHW—No native runNative Revit model 1ce22c7e (MEP PASS) and the Run 4 sizing calculations; carried unchanged into the proposed model
FLOW-SEC
Secondary design flows CHW 3.936 l/s, LTHW 1.368 l/s
CHW+LTHW—No native runCalculated (design model pumps_and_fans): CHWP 3.936 l/s, LTHWP 1.368 l/s from native loads; header sections CHW DN80, LTHW DN50
HP01-CHW-SIZE
HP-01 CHW connection size 2 1/2" grooved
CHW—No native runPublished data sheet (catalogue record aermec-nrp-0600-a-4pipe): 2 1/2" grooved (source S1); position NOT HELD
HP01-ELEC-FLA
HP-01 full-load current 100 A (data sheet)
electrical—No native runPublished data sheet value; selection CONFIRMATION REQUIRED
PROVISIONAL 27 — declared design assumption with stated size / location; pending verification
ItemSystemSizeNative statusBasis / pending
HDR-chw_flow_m0
Header HDR-01 → hw-m0.CHW_FLOW (DN65)
CHW FLOWDN65Connected nativelyMain position and size from the accepted native model; the header is a planning envelope with a PROVISIONAL DESIGN INTERFACE at the main's former open end Pending: header manufacture / fabrication drawing; isolating valve per branch
HDR-chw_return_m0
Header HDR-01 → hw-m0.CHW_RETURN (DN65)
CHW RETURNDN65Connected nativelyMain position and size from the accepted native model; the header is a planning envelope with a PROVISIONAL DESIGN INTERFACE at the main's former open end Pending: header manufacture / fabrication drawing; isolating valve per branch
HDR-lthw_flow_m0
Header HDR-01 → hw-m0.LTHW_FLOW (DN32)
LTHW FLOWDN32Connected nativelyMain position and size from the accepted native model; the header is a planning envelope with a PROVISIONAL DESIGN INTERFACE at the main's former open end Pending: header manufacture / fabrication drawing; isolating valve per branch
HDR-lthw_return_m0
Header HDR-01 → hw-m0.LTHW_RETURN (DN32)
LTHW RETURNDN32Connected nativelyMain position and size from the accepted native model; the header is a planning envelope with a PROVISIONAL DESIGN INTERFACE at the main's former open end Pending: header manufacture / fabrication drawing; isolating valve per branch
HDR-chw_flow_ahu
Header HDR-01 → hw-ahu.CHW_FLOW (DN50)
CHW FLOWDN50Connected nativelyMain position and size from the accepted native model; the header is a planning envelope with a PROVISIONAL DESIGN INTERFACE at the main's former open end Pending: header manufacture / fabrication drawing; isolating valve per branch
HDR-chw_return_ahu
Header HDR-01 → hw-ahu.CHW_RETURN (DN50)
CHW RETURNDN50Connected nativelyMain position and size from the accepted native model; the header is a planning envelope with a PROVISIONAL DESIGN INTERFACE at the main's former open end Pending: header manufacture / fabrication drawing; isolating valve per branch
HDR-lthw_flow_ahu
Header HDR-01 → hw-ahu.LTHW_FLOW (DN32)
LTHW FLOWDN32Connected nativelyMain position and size from the accepted native model; the header is a planning envelope with a PROVISIONAL DESIGN INTERFACE at the main's former open end Pending: header manufacture / fabrication drawing; isolating valve per branch
HDR-lthw_return_ahu
Header HDR-01 → hw-ahu.LTHW_RETURN (DN32)
LTHW RETURNDN32Connected nativelyMain position and size from the accepted native model; the header is a planning envelope with a PROVISIONAL DESIGN INTERFACE at the main's former open end Pending: header manufacture / fabrication drawing; isolating valve per branch
pri-hp.CHW_FLOW
HP-01 ↔ XP-CONN external primary — CHW FLOW
CHW FLOWDN80Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
pri-hp.CHW_RETURN
HP-01 ↔ XP-CONN external primary — CHW RETURN
CHW RETURNDN80Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
pri-hp.LTHW_FLOW
HP-01 ↔ XP-CONN external primary — LTHW FLOW
LTHW FLOWDN50Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
pri-hp.LTHW_RETURN
HP-01 ↔ XP-CONN external primary — LTHW RETURN
LTHW RETURNDN50Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
pri-a.CHW_FLOW
XP-CONN ↔ 4-port buffer primary — CHW FLOW
CHW FLOWDN80Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
pri-a.CHW_RETURN
XP-CONN ↔ 4-port buffer primary — CHW RETURN
CHW RETURNDN80Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
pri-a.LTHW_FLOW
XP-CONN ↔ 4-port buffer primary — LTHW FLOW
LTHW FLOWDN50Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
pri-a.LTHW_RETURN
XP-CONN ↔ 4-port buffer primary — LTHW RETURN
LTHW RETURNDN50Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
sec-b.CHW_FLOW
buffer → secondary pump suction — CHW FLOW
CHW FLOWDN80Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
sec-c.CHW_FLOW
secondary pump discharge → header — CHW FLOW
CHW FLOWDN80Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
sec-r.CHW_RETURN
header → buffer secondary return — CHW RETURN
CHW RETURNDN80Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
sec-b.LTHW_FLOW
buffer → secondary pump suction — LTHW FLOW
LTHW FLOWDN50Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
sec-c.LTHW_FLOW
secondary pump discharge → header — LTHW FLOW
LTHW FLOWDN50Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
sec-r.LTHW_RETURN
header → buffer secondary return — LTHW RETURN
LTHW RETURNDN50Connected nativelyHydraulic principle MF-1 + MF-3 (D-HYD-PRINCIPLE): HP-01 → XP-CONN → 4-port buffer (decoupler) → secondary pumps → header Pending: primary rated flow and connection positions (manufacturer); pressure loss (fittings, valves, plant) NOT HELD
VALVES-ISO
Isolating valves each side of every pump set, buffer and the header connections
CHW+LTHW—No native runEngineering requirement recorded as a schedule item; not modelled natively (no Hexanta valve / accessory families); products NOT SELECTED Pending: product selection; native accessory families
STRAINERS
Strainers on each secondary pump suction
CHW+LTHW—No native runEngineering requirement recorded as a schedule item; not modelled natively (no Hexanta valve / accessory families); products NOT SELECTED Pending: product selection; native accessory families
NRV
Non-return valves on the duty / standby pump discharges
CHW+LTHW—No native runEngineering requirement recorded as a schedule item; not modelled natively (no Hexanta valve / accessory families); products NOT SELECTED Pending: product selection; native accessory families
BALANCING
Terminal balancing by PICVs (FCUs, AHU) — existing valve schedule
CHW+LTHW—No native runEngineering requirement recorded as a schedule item; not modelled natively (no Hexanta valve / accessory families); products NOT SELECTED Pending: product selection; native accessory families
DRAIN-VENT
Drain cocks at low points, automatic air vents at high points of the primary pipework
CHW+LTHW—No native runEngineering requirement recorded as a schedule item; not modelled natively (no Hexanta valve / accessory families); products NOT SELECTED Pending: product selection; native accessory families
BLOCKED 9 — cannot be designed or placed with the information held
ItemSystemSizeNative statusBasis / pending
HP01-ELEC-SUPPLY
HP-01 electrical supply, isolator and route
electrical—No native runNo electrical design / LV distribution model; supply route NOT HELD
HP01-BMS
HP-01 controls / BMS interface
controls—No native runInterface (protocol, points) NOT HELD; controls schematic INDICATIVE
HP01-DEFROST
HP-01 defrost / condensate drainage
drainage—No native runDrain point, falls and frost protection NOT HELD (public health engineer)
PRESS-EXP
Pressurisation unit and expansion (PU-01/02)
CHW+LTHW—No native runSystem water volume, static height and temperature range INPUT REQUIRED; sizing BLOCKED
SAFETY-VALVES
Safety / pressure-relief valves
CHW+LTHW—No native runDepend on the sealed-system design (pressurisation BLOCKED); not invented
FILL
Filling connection (cold feed via pressurisation unit)
CHW+LTHW—No native runDepends on the pressurisation unit selection (BLOCKED)
DOSING
Dosing pot DP-01/02 connection
CHW+LTHW—No native runNo connection route in the design model; water-treatment specification NOT HELD
PUMP-HEAD
Secondary pump duty points
CHW+LTHW—No native runHead lower bound only (CHW 82.8 kPa, LTHW 40.2 kPa); fitting / plant losses and pump curves NOT HELD
FCU-COND-STACK
FCU condensate discharge to the soil stack (tundish CD-E)
drainage—No native runTundish location and stack connection INPUT REQUIRED (public health)