THERMAL MODELLING

Room heating and cooling loads

Room-by-room loads from the native IESVE CIBSE Loads runs, with their status and evidence.

Results: Change run — criteria revision 3 — RECORDED (verified evidence, not re-run) · S3-P03C-CR003 (change on the P03A coordination candidate)

Native model and simulation status

Native runs verified IESVE 2026 (trial licence) CIBSE Loads: heat loss and heat gain, ground floor (WF1_CIBSE_GF_RUN4E, CIBSE (Loads Methodology = CIBSE; ApacheCalc)). Weather: London Heathrow, 51.48 N 0.45 W, 25 m.

Loads are PROVISIONAL: trial-licence results, kept locally (decision D-01), not engineer reviewed. Hexanta never recalculates a native load: when criteria change, affected rooms are marked STALE until IESVE is re-run.

Re-import native room-load records

After IESVE is re-run for a criteria change, upload its load records here as new input revisions; the next run uses them. Each upload is a revision with its source note. A plain upload does not clear a STALE room: that needs a verified native IESVE package (Software).

Sum of room sensible peaks

51.4 kW

Sum of room latent

9.5 kW

Coincident cooling (IESVE)

49.1 kW

Whole-model coincident peak

Heating (steady / boosted)

16.6 / 33.1 kW

Conditioned area

756 m²

Coincident cooling is IESVE's whole-model coincident peak; the room peaks occur at different times, so their sum exceeds it.

Room loads
RoomUseArea m²Occ.Sensible WLatent WTotal WCooling W/m²PeakHeating WHeating W/m²OA l/sBasisStatus
Open-plan office zone 1 r01aoffice135.0349,4981,87011,36884.27 / 13:302,63619.5380.5Nativecurrent
Open-plan office zone 2 r01boffice135.0349,3481,87011,21883.17 / 13:302,63019.5380.5Nativecurrent
Open-plan office zone 3 r01coffice135.0349,3061,87011,17682.87 / 13:302,63019.5380.5Nativecurrent
Open-plan office zone 4 r01doffice135.0176,9699357,90458.57 / 13:302,63719.5210.5Nativecurrent
Meeting room 1 r02meeting36.0244,8301,3206,150170.87 / 16:301,07930.0250.8Nativecurrent
Meeting room 2 r03meeting36.0244,5841,3205,904164.07 / 16:3080122.2250.8Nativecurrent
Reception r04circulation36.043,3032203,52397.98 / 15:301,07930.050.8Nativecurrent
WC female r05wc30.00587058719.67 / 15:3085828.60.0Nativecurrent
WC male r06wc30.00545054518.27 / 15:3076625.50.0Nativecurrent
Accessible WC r07wc18.00367036720.47 / 14:3046325.70.0Nativecurrent
East lift lobby r08circulation30.022,0441102,15471.89 / 13:301,04634.929.0Nativecurrent
Mechanical plantroom r09plant108.00————-——0.0Nativecurrent

Source of every load: IESVE native report p7 (local evidence, D-01). Heating is steady-state; boosted (pre-heat) values are in the calculation workbook.

Engineer review of room loads

Record an engineer decision on these loads. It is stored with the reviewer's (unverified, development) identity; it does not change any value. To correct an input, edit Criteria — a change creates a new revision and shows its impact first.