MECHANICAL SYSTEM DESIGN

Systems, equipment and distribution

Deterministic Hexanta calculations from the native loads and the design criteria. Calculated, assumed and blocked values are labelled; no manufacturer rating is invented.

Results: Change run — criteria revision 3 — RECORDED (verified evidence, not re-run) · S3-P03C-CR003 (change on the P03A coordination candidate)

No equipment is selected (no selection register supplied)

No manufacturer-verified rating is held: every FCU, AHU, heat pump, pump and fan is NOT SELECTED. Pump and fan duties stay BLOCKED until fitting, terminal and plant-side losses are supplied.

Ventilation and air balance

Outdoor air

1,933.4 l/s

Calculated

General extract

1,621.4 l/s

Calculated

WC extract

312.0 l/s

Calculated

Ventilation rule values are SYNTHETIC (XX-TEST) until a licensed source is held.

AHU-01 — option A1 (scenario options, undecided)

SCENARIO OPTIONS — D-05a–g undecided; fan heat excluded; HR effectiveness is a regulatory-minimum scenario

Summer outdoor 32.1 °C db / 21 °C wb (IESVE Rev02 design weather (ASHRAE design weather database; heating 99.6 %, cooling 0.4 % monthly percentile)); room 24 °C, 50 % RH.

OptionCooling coil kWHeating coil (winter) kWSummer reheat kWWarnings
A1 Neutral supply 24/21 C, room-neutral moisture, LTHW reheat (founder provisional temperatures)39.3614.2224.11condensation, frost_risk, reheat_required
A2 Neutral supply 24/21 C, drier supply absorbs room latent (FCUs sensible only)56.8314.2231.34condensation, frost_risk, reheat_required
A3 Cool supply 14 C summer (close to off-coil, minimal reheat), room-neutral moisture; 21 C winter39.3614.220.63condensation, frost_risk, reheat_required

Central plant (heat source and duties)

PROVISIONAL — base duties from native loads + AHU scenario options; pipe heat gains/losses, fan heat and distribution losses EXCLUDED (INPUT REQUIRED)

Heat source (proposed for coordination): four_pipe_ashp.

Cooling, basis A

100.3 kW

Room peaks + AHU coil

Cooling, basis B

88.4 kW

IESVE coincident + AHU (approx.)

Heating (AHU off in pre-heat)

33.1 kW

Margin (selected)

20 %

Assumed

PROVISIONAL — defaults, NOT engineer-selected. Room duties use ONE design peak per room: heating = the IESVE intermittent (boosted) plant load, which already includes the intermittent uplift over the steady-state load; cooling = room total (sensible + latent) at the room peak. The plant duty = the selected basis + the AHU coil of the selected AHU option (outdoor air counted once, on the AHU coil). The margin is applied ONCE, to that plant duty only; it is never applied to room loads, the AHU coil or the uplift separately.

Heating plantkWBasis
Room design heating peaks (Σ, one per room)33.1IESVE boosted plant load
of which intermittent uplift (audit only)16.5already inside the design peaks — not added again
steady-state (audit only)16.6IESVE steady-state
AHU heating coil14.2AHU option A1
Heating base duty47.3Σ room design heating peaks (intermittent uplift included) + AHU heating coil — preheat and AHU coincide (conservative)
Margin 20 %9.5applied once
Selected plant duty56.8plant_selection.margin_option = 20 %
Cooling plantkWBasis
Room design cooling peaks (Σ sensible + latent)60.9sensible 51.4 + latent 9.5 kW
Coincident building cooling (IESVE)49.1simultaneity 0.805
AHU cooling coil (outdoor air, counted once)39.4AHU option A1
Cooling base duty88.4IESVE coincident building cooling peak + AHU cooling coil — central plant (simultaneity from the simulation)
Margin 20 %17.7applied once
Selected plant duty106.1plant_selection.margin_option = 20 %

Change the basis or the margin under Criteria → Plant selection; the change is recorded with its reason and re-run.

PROVISIONAL — scenarios for comparison; none is engineer-approved

AHU optionStrategyBase kW+0 %+10 %+20 %Summer reheat kW
A1Heating — AHU running during warm-up47.347.352.056.8 ●24.1
A1Heating — AHU held off during warm-up33.133.136.439.724.1
A1Cooling — coincident building peak88.488.497.2106.1 ●24.1
A1Cooling — sum of room peaks (non-coincident)100.3100.3110.3120.324.1
A2Heating — AHU running during warm-up47.347.352.056.831.3
A2Heating — AHU held off during warm-up33.133.136.439.731.3
A2Cooling — coincident building peak96.496.4106.0115.631.3
A2Cooling — sum of room peaks (non-coincident)108.2108.2119.0129.931.3
A3Heating — AHU running during warm-up47.347.352.056.80.6
A3Heating — AHU held off during warm-up33.133.136.439.70.6
A3Cooling — coincident building peak65.165.171.678.10.6
A3Cooling — sum of room peaks (non-coincident)76.976.984.692.30.6

● = the current selection (not approved). Each value = base × (1 + margin): the margin is applied once. Summer reheat runs with cooling in that AHU option (energy / Part L review).

Fan coil units — required duties

FCURoomCooling sens. WCooling total WHeating WSupply l/sOA l/sCHW l/sLTHW l/sBasisSelection
FCU-GF-01Open-plan office zone 14,7495,6842,663393.4190.30.2270.064Calculatednot selected
FCU-GF-02Open-plan office zone 14,7495,6842,663393.4190.30.2270.064Calculatednot selected
FCU-GF-03Open-plan office zone 24,6745,6092,658387.2190.30.2240.064Calculatednot selected
FCU-GF-04Open-plan office zone 24,6745,6092,658387.2190.30.2240.064Calculatednot selected
FCU-GF-05Open-plan office zone 34,6535,5882,658385.4190.30.2230.064Calculatednot selected
FCU-GF-06Open-plan office zone 34,6535,5882,658385.4190.30.2230.064Calculatednot selected
FCU-GF-07Open-plan office zone 43,4853,9522,663288.6105.30.1580.064Calculatednot selected
FCU-GF-08Open-plan office zone 43,4853,9522,663288.6105.30.1580.064Calculatednot selected
FCU-GF-09Meeting room 14,8306,1502,074400.1250.80.2450.050Calculatednot selected
FCU-GF-10Meeting room 24,5845,9041,616379.7250.80.2350.039Calculatednot selected
FCU-GF-11Reception3,3033,5232,074273.650.80.1400.050Calculatednot selected
FCU-GF-12East lift lobby2,0442,1541,947169.329.00.0860.047Calculatednot selected

a room's loads and outdoor air are divided equally between its FCUs (no per-facade split: IESVE models each zone as one room)

Distribution networks — sizing and index circuits

NetworkMediumDesign flow l/sSectionsIndex endRoute mFriction lower bound PaPressure
OA Outdoor air supply (AHU-01 to FCU inlet plenums)air1,933.40019FCU-GF-0947.035lower bound (7 missing)
GEX General extract (rooms to AHU-01 heat recovery)air1,621.40013EG-GF-0762.648lower bound (6 missing)
WCX WC extract (WCs to EF-01, discharge to atmosphere)air312.0005XG-GF-0611.87lower bound (2 missing)
HW-CHW Four-pipe CHW and LTHW distribution (shared route; CHW omits LTHW-only branches) — CHWwater3.93622FCU-GF-0951.413,185lower bound (9 missing)
HW-LTHW Four-pipe CHW and LTHW distribution (shared route; CHW omits LTHW-only branches) — LTHWwater1.36827FCU-GF-0951.417,030lower bound (9 missing)
SD-01 FCU-GF-01 discharge to supply diffusersair393.3903SD-GF-01B4.44lower bound (1 missing)
SD-02 FCU-GF-02 discharge to supply diffusersair393.3903SD-GF-02B4.44lower bound (1 missing)
SD-03 FCU-GF-03 discharge to supply diffusersair387.1773SD-GF-03A4.44lower bound (1 missing)
SD-04 FCU-GF-04 discharge to supply diffusersair387.1773SD-GF-04A4.44lower bound (1 missing)
SD-05 FCU-GF-05 discharge to supply diffusersair385.4373SD-GF-05B4.44lower bound (1 missing)
SD-06 FCU-GF-06 discharge to supply diffusersair385.4373SD-GF-06B4.44lower bound (1 missing)
SD-07 FCU-GF-07 discharge to supply diffusersair288.6433SD-GF-07A4.42lower bound (1 missing)
SD-08 FCU-GF-08 discharge to supply diffusersair288.6433SD-GF-08A4.42lower bound (1 missing)
SD-09 FCU-GF-09 discharge to supply diffusersair400.0993SD-GF-09B4.24lower bound (1 missing)
SD-10 FCU-GF-10 discharge to supply diffusersair379.7223SD-GF-10B5.14lower bound (1 missing)
SD-11 FCU-GF-11 discharge to supply diffusersair273.6083SD-GF-11A3.02lower bound (1 missing)
SD-12 FCU-GF-12 discharge to supply diffusersair169.3171SD-GF-12A1.71lower bound (1 missing)

Pumps and fans

TagDescriptionFlow l/sPressureDutyMissing inputs
CHWP-01A/BCHW secondary variable-speed pumps (duty/standby; PICV terminals)3.936BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting (bends/tees); terminal device loss (coil + control valve + isolation, or grille/regulator); plant-side losses (heat pump/chiller, strainers, headers)
LTHWP-01A/BLTHW secondary variable-speed pumps (duty/standby; PICV terminals)1.368BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting (bends/tees); terminal device loss (coil + control valve + isolation, or grille/regulator); plant-side losses (heat pump/chiller, strainers, headers)
AHU-01 supply fanAHU supply fan (external: OA ductwork to FCU plenums)1,933.400BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting (bends/tees); terminal device loss (coil + control valve + isolation, or grille/regulator); AHU internal losses (filters, coils, heat recovery, attenuators) and intake/exhaust louvres
AHU-01 extract fanAHU extract fan (external: general extract ductwork)1,621.400BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting (bends/tees); terminal device loss (coil + control valve + isolation, or grille/regulator); AHU internal losses (filters, coils, heat recovery, attenuators) and intake/exhaust louvres
EF-01WC extract fan312.000BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting (bends/tees); terminal device loss (coil + control valve + isolation, or grille/regulator); AHU internal losses (filters, coils, heat recovery, attenuators) and intake/exhaust louvres
FCU-GF-01 fan (external)FCU fan external static: discharge plenum, branches and diffusers393.390BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-02 fan (external)FCU fan external static: discharge plenum, branches and diffusers393.390BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-03 fan (external)FCU fan external static: discharge plenum, branches and diffusers387.177BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-04 fan (external)FCU fan external static: discharge plenum, branches and diffusers387.177BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-05 fan (external)FCU fan external static: discharge plenum, branches and diffusers385.437BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-06 fan (external)FCU fan external static: discharge plenum, branches and diffusers385.437BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-07 fan (external)FCU fan external static: discharge plenum, branches and diffusers288.643BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-08 fan (external)FCU fan external static: discharge plenum, branches and diffusers288.643BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-09 fan (external)FCU fan external static: discharge plenum, branches and diffusers400.099BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-10 fan (external)FCU fan external static: discharge plenum, branches and diffusers379.722BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-11 fan (external)FCU fan external static: discharge plenum, branches and diffusers273.608BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP
FCU-GF-12 fan (external)FCU fan external static: discharge plenum, branches and diffusers169.317BLOCKED — lower bound onlyBlocked NOT CALCULATEDfitting ζ for every counted fitting; diffuser, plenum box and damper ΔP (manufacturer); FCU return-air path (ceiling plenum / grille) and filter ΔP

Quantities

Route lengths from the design model (plan route length; flow + return for water). Fittings, risers to terminals and drops are excluded: a lower bound for take-off, not a BOQ.

Ductwork

268.7 m

Pipework (flow + return)

446.4 m

GEX grille

7 no.

WCX grille

3 no.

ahu

1 no.

buffer

2 no.

connection

1 no.

dosing

1 no.

Ductwork by size (m)
1000x2507.8
1000x30020.7
1200x30011.2
300x2002.4
300x25014.9
300x3008.4
400x25014.2
400x3005.2
500x3007.8
700x2507.5
800x2507.2
900x2507.5
Ø1256.0
Ø16012.4
Ø20019.4
Ø250104.3
Ø31511.7
Pipework by size (m)
CHW DN151.8
CHW DN2032.0
CHW DN2572.6
CHW DN3215.7
CHW DN4015.0
CHW DN5043.2
CHW DN6527.5
CHW DN800.8
LTHW DN15141.4
LTHW DN209.9
LTHW DN2530.0
LTHW DN3255.7
LTHW DN500.8