CALCULATIONS AND SCHEDULES
Calculations, schedules and BOQ
The current calculation package, equipment Required / Offered schedules and BOQ, with each run's own calculation workbook and schedules — by topic, with revision, source, native evidence status, previews and downloads.
P07 PROPOSED — not checked or approved by an engineer, not for construction
Checked by / approved by: NOT RECORDED — no verified engineer identity; nothing here is engineer approved or issued for construction.
PROPOSED — not checked or approved by an engineer, not for construction. Workbooks holding licensed CIBSE Guide C data stay local (named, with the reason); their review pages and every other workbook download here with their SHA-256.
Heating and cooling loads
Room heating and cooling loads from native IESVE (RUN4E), plant duties and scenarios
Pump and fan index runs and duties (lower bounds until manufacturer data is held)
Index runs and duties (Run 4, plan r11-r7) — PROVISIONAL - not engineer reviewed; duties are lower bounds unless stated
Pump / fan
System
Flow
Governing end
Index pressure
Status
Missing
CHWP-01A/B
HW-CHW
3.935979 l/s
FCU-GF-09
82.8 kPa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (34 cases, flagged); coil water Δp (FCU-GF-09); strainer (FCU-GF-09); isolation valves / flow measurement (FCU-GF-09); plant side (heat pump / chiller, headers, strainers) (CHWP-01A/B)
LTHWP-01A/B
HW-LTHW
1.367981 l/s
FCU-GF-09
40.2 kPa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (22 cases, flagged); coil water Δp (FCU-GF-09); strainer (FCU-GF-09); isolation valves / flow measurement (FCU-GF-09); plant side (heat pump / chiller, headers, strainers) (LTHWP-01A/B)
AHU-01 supply fan
OA
1933.4 l/s
FCU-GF-10
83.4 Pa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (29 cases, flagged); terminal (grille / FCU spigot) Δp (FCU-GF-10); unit internal + louvres / attenuators (AHU-01)
AHU-01 extract fan
GEX
1621.4 l/s
EG-GF-06
128.2 Pa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (20 cases, flagged); terminal (grille / FCU spigot) Δp (EG-GF-06); unit internal + louvres / attenuators (AHU-01)
EF-01
WCX
312 l/s
XG-GF-05
25.1 Pa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (12 cases, flagged); terminal (grille / FCU spigot) Δp (XG-GF-05); unit internal + louvres / attenuators (EF-01)
Lower bounds until the missing items are held; licensed CIBSE Guide C fitting coefficients stay local and are not shown. Source wf1-MECH-SCHEDULES-20261020-r11-r7-r5/pressure-losses.json (SHA-256 eb1cf9451a57).
Calculation package (P07)
PROPOSED — not accepted, not checked, not approvedP07Run 4