CALCULATIONS AND SCHEDULES
Calculations, schedules and BOQ
The current calculation package, equipment Required / Offered schedules and BOQ, with each run's own calculation workbook and schedules — by topic, with revision, source, native evidence status, previews and downloads.
P07 PROPOSED — not checked or approved by an engineer, not for construction
Checked by / approved by: NOT RECORDED — no verified engineer identity; nothing here is engineer approved or issued for construction.
PROPOSED — not checked or approved by an engineer, not for construction. Workbooks holding licensed CIBSE Guide C data stay local (named, with the reason); their review pages and every other workbook download here with their SHA-256.
Showing the documents for EF-01 — its data sheet "M17 EF-01" is open below.
Hydraulic and fitting losses, index runs
Pump and fan index runs and duties (lower bounds until manufacturer data is held)
Index runs and duties (Run 4, plan r11-r7) — PROVISIONAL - not engineer reviewed; duties are lower bounds unless stated
Pump / fan
System
Flow
Governing end
Index pressure
Status
Missing
CHWP-01A/B
HW-CHW
3.935979 l/s
FCU-GF-09
82.8 kPa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (34 cases, flagged); coil water Δp (FCU-GF-09); strainer (FCU-GF-09); isolation valves / flow measurement (FCU-GF-09); plant side (heat pump / chiller, headers, strainers) (CHWP-01A/B)
LTHWP-01A/B
HW-LTHW
1.367981 l/s
FCU-GF-09
40.2 kPa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (22 cases, flagged); coil water Δp (FCU-GF-09); strainer (FCU-GF-09); isolation valves / flow measurement (FCU-GF-09); plant side (heat pump / chiller, headers, strainers) (LTHWP-01A/B)
AHU-01 supply fan
OA
1933.4 l/s
FCU-GF-10
83.4 Pa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (29 cases, flagged); terminal (grille / FCU spigot) Δp (FCU-GF-10); unit internal + louvres / attenuators (AHU-01)
AHU-01 extract fan
GEX
1621.4 l/s
EG-GF-06
128.2 Pa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (20 cases, flagged); terminal (grille / FCU spigot) Δp (EG-GF-06); unit internal + louvres / attenuators (AHU-01)
EF-01
WCX
312 l/s
XG-GF-05
25.1 Pa
PARTIAL (lower bound)
fittings: Guide C outside its stated range (12 cases, flagged); terminal (grille / FCU spigot) Δp (XG-GF-05); unit internal + louvres / attenuators (EF-01)
Lower bounds until the missing items are held; licensed CIBSE Guide C fitting coefficients stay local and are not shown. Source wf1-MECH-SCHEDULES-20261020-r11-r7-r5/pressure-losses.json (SHA-256 eb1cf9451a57).
Calculation package (P07)
PROPOSED — not accepted, not checked, not approvedP07Run 4